| TANKS FOR GENERATOR SETS AND HEATING SYSTEMS |
|
|
Tanks for external generator sets and heating systems built with top quality carbon steel in compliance with Presidential Decree 1391 of 22
December 1970 and according to what is provided for in memorandum no. 73 of 29/07/1971. They are complete with impounding basin with a
capacity of not less than 50% of the geometric capacity of the tank. The basin is supplied already bolted onto the tank and if required a
roof can be mounted. Painted with a coat of rustproof paint and a gray Ral 7035 finishing coat.
|
 |
The Tanks are equipped with:
- 400 mm Ø hatch with load limiting valve reducing the tank geometric capacity to 90%, shut-off vent with flame-break mesh, 3” load with ring nut and pad lockable plug, level indicator visible from the outside, inside protection pipe for the float, suction pipe with 1" foot valve and no. 2 x 1” suction and return coupling.
- Bottom discharge with plug.
- Ready for earth connection.
- Galvanised sheet protection roof (optional).
- Final testing certificate and calibration table.
 |
 |
 |
| Top hatch |
Earthing |
Drainage |
| |
nominal |
Diameter cm. |
Total length |
Length cm. |
Width cm. |
Height cm. |
| GET 1 |
1770 |
127 |
152 |
200 |
140 |
38 |
| GET 2 |
2380 |
127 |
203 |
235 |
140 |
38 |
| GET 3 |
3350 |
160 |
180 |
240 |
175 |
40 |
| GET 5 |
5350 |
160 |
280 |
340 |
175 |
45 |
| GET 7 |
6800 |
170 |
310 |
370 |
200 |
50 |
| GET 9 |
8870 |
190 |
320 |
380 |
210 |
55 |
The capacities described above are nominal; useful capacity corresponds to about 90% for the load limiting valve.
|